Mitsubishi Electronics TG-2000A Air Conditioner User Manual


 
119
Set blocks excluded from energy saving operation
1) Select the excluded functions with the
button.
Select the whether functions are excluded from energy saving operation by clicking the
button.
2) Select the excluded temperature difference with the
button.
Select the conditional temperature difference to be excluded from energy saving operation by
clicking
.
Setting temperature difference: 3 deg. to 9 deg. (1 deg. increments)
Setting the energy saving function for the outdoor unit
1) Select the outdoor unit to be set for each level with the
button.
Select the outdoor unit to be set for each level by clicking
.
The number of levels set with the control start electric amount can be set.
2) Select the control details with the
button.
Select the control details for energy saving operation by clicking
.
Control details: No control
Performance save rate 0.6 to 0.9 (0.1 increments)
3) Select the control time with the
button.
Select the control time for energy saving operation by clicking
.
The following times can be set when a setting other than "No control" is selected for the control
details.
Control time: 3 minutes
6 minutes
9 minutes
15 minutes
30 minutes
4) Repeat steps 1) to 3).
Repeat steps 1) to 3) for the outdoor units set for energy saving.
Finish setting the peak cut function, and send the set details to the G-50A
1) Click on the [OK] button.
When finished with the settings, click on the [OK] button.
The set details will be sent to the G-50A and the Peak Cut Setting screen will close.
Note:
The target indoor units are displayed in the "Control group" field.
If the settings are the same for each block, use the "Copy" and "Paste" functions to make the
process easier.
When ventilator/thermo OFF control is selected, the thermo OFF (performance save) command will
be sent to the free plan model, and the ventilator mode changeover command will be sent to the
K
control model. When thermo OFF control is selected, the remote controller's display will not change,
so energy saving control can be carried out without anyone knowing about it. When temperature
control is selected, the set temperature will change +2°C during cooling, and -2°C during heating.
Note:
These settings excluded from energy saving operation are batch settings for each AG-150A/G-50A.
Note:
The indoor units connected to the target outdoor units are displayed in the "Control group" field.
If the settings are the same for each outdoor unit, use the "Copy" and "Paste" functions to make the
process easier.
The setting method for the A-control outdoor units is the same as that for the energy save setting,
and the same cautionary notes apply to both.