Mitsubishi Electronics TG-2000A Air Conditioner User Manual


 
74
5) Set-up the CSV form of AG-150A/G-50A.
Setting the unit of measure and delimiter for CSV.
Decimal point : dot or comma.
CSV delimiter : comma or semi-colon.
* If comma is selected as the decimal delimiter, semicolon will automatically be selected as the CSV
delimiter (fixed).
If comma is selected as the CSV delimiter, period will automatically be selected as the decimal delimiter
(fixed).
6) Click theOKbutton.
When the setting is completed, click theOKbutton.
Click theCancelbutton to cancel this procedure and return to the initial window.
8.8.4 PI controller (Meter) Set-up (Step 3)
Set-up the PI controller (MCP) function
Operation Method
1) Select AG-150A/G-50A No. with the / button.
Select AG-150A/G-50A No. connected to PI Controller with
the / button.
2) Set-up the detail of measurement
Click the measurement to make a setting.
The screen of measurement will appear and make the settings
below.
Usage type: Select one from Air conditioner/Electricity1/
Electricity2/Gas/Water/Heat/Other.
Measurement name: 20 characters or less.
Placement: 20 characters or less.
Pulse: Set the value of measurement per pulse (kWh etc.)
within the rang of 0.01100.00.
The pulse setting of the PI controller that is registered to the AG-150A/G-50A can be monitored.
Press the [All monitors] button to monitor all AG-150A/G-50A units, and press the [Monitor] button to monitor
only the selected AG-150A/G-50A unit. The acquired information will appear on the “PI controller (meter)”
screen. (The pulse setting of the PI controller that has not been registered to TG-2000A cannot be
monitored.)
3) Click the [OK] button.
When the setting is completed, click theOKbutton.
* Click theCancelbutton to cancel the procedure and return to the initial window.
Note:
Always set the meter pulse unit. If not set, the cumulative usage amount will not be correctly
measured and the charging function will not work properly.
• When using the Measurement Meter, give a test run for proper period to check the finite difference
of the value measured by the meter matches monitor value.
Check that the dipswitches for the channel that is used by the PI controller are set as follows: “Us
e
of input contact : Yes”; “Pulse unit (weight) value setting: SC setting”.
If “Use of input contact” is set to any setting other than “Yes,” pulse input to the PI controller will be invalid and
pulse count cannot be taken.
If “Pulse unit (weight) value setting” is set to a setting other than “SC setting,” the pulse setting from
TG-2000A will be invalid, and the PI controller’s dipswitch setting will override the TG-2000A’s setting.
Refer to the PI controller Installation/Instruction Manual for how to set the dipswitches of the PI controller.
Use a watt-hour meter with the pulse size of 1 kWh or below to measure the apportioned electric
power.
MCP setting screen
MCP advanced setting screen