64
8.7 System Configuration Set-up
Set the information of the air-conditioning system to be monitored using this integrated centralized
control software TG-2000A. It is possible for this setting to monitor the system information possessed
by the AG-150A/G-50A.
8.7.1 Setting Procedure and Restrictions
Confirm the precautions and procedure before setting the system configuration.
Perform the confirmation before setting the system configuration.
[Procedure]
1) Select the [System configuration set-up] button.
Click the [System configuration set-up] button
located in the system setting group on the initial
window.
2) Select the [OK] button after confirming the
display contents.
Check the contents of the alarm displayed.
When there are not any problems found, click
the [OK] button to advance to the setting.
* When the [Cancel] button is clicked, this setting
is terminated to return to the initial screen.
Execute the System configuration set-up in
accordance with the following procedure.
Step 1: AG-150A/G-50A data collection
Step 2: Unit composition of AG-150A/G-50A
Step 3: Set-up of refrigerant system
Step 4: Set-up of group
Step 5: Interlocked setting
8.7.2 AG-150A/G-50A data collection (Step 1)
It is possible to collect the system information (group information, interlocking ventilation unit
setting information, etc.) set for the AG-150A/G-50A with the integrated centralized control software
TG-2000A during the initial setting.
Collect the information from the AG-150A/G-50A during the initial setting.
(* Carry this step out only for the first initialization.
)
[Procedure]
1) Select the [Collecting of information from AG-150A/G-50A]
button.
To collect the system information from the AG-150A/G-50A
during the initial setting, select AG-150A/G-50A, and click
the [Collecting of information from AG-150A/G-50A] button.
After completing the information collecting, the operation
advances automatically to the next step. Wait a moment,
as it takes time for information collecting.
* When the [Cancel] button is clicked, this setting is
terminated to return to the initial screen.
Skip the collecting information from the AG-150A/G-50A.
[Procedure]
1) Select the [Next] button.
If it is not necessary to collect the information, click the [Next] button.
Caution:
• Note that using the AG-150A/G-50A data collecting function may cause the system information
possessed in theTG-2000A to be cleared. The AG-150A/G-50A information is overwritten when
the information is collected, so make the initial settings again (schedule, charge, peak cut o
r
etc.).
• It can only collect the information when the AG-150A/G-50A units are connected.
• It is recommended to execute this function after the test operation of the air conditioner and the
AG-150A/G-50A have been completed normally.
AG-150A/G-50A Data collection screen
Preparation screen