Mitsubishi Electronics TG-2000A Air Conditioner User Manual


 
101
8.14.6 Electrical specification of indoor units (Step 5)
Set the parameter for all indoor units connected to the AG-150A/G-50A.
Set indoor unit operating capacity and power input
and auxiliary heater.
[Procedure]
1) Select the AG-150A/G-50A number using the
/
” button.
Using the “
/
” button, select the AG-150A/G-50A
number for the indoor unit whose capacity is to be
set.
2) Set the Capacity, power input and auxiliary heater.
Click the indoor unit parameter cells.
Enter the indoor unit parameter of “Cooling
Capacity”, “Power input (Cooling)” and “Auxiliary
heater”.
* Since the value of each capacity is displayed automatically
for the indoor units for which the model name set in section
“8.7.2 Model Name” exists in the database, check such value.
3) Click [OK] button after setting all indoor units.
After completing the capacity setting for all indoor units, click the [OK] button.
* If the [Cancel] button is clicked, the settings are interrupted and the screen returns to the initial window.
8.14.7 Charge Blocks (Step 6)
Follow these steps to set charging blocks using the
control blocks.
Air-conditioning charges are calculated for each charging
block.
Set the charge blocks.
[Procedure]
1) Select the charging block setting method.
Select either “The same as that of the block
for operation” option or “Create separately” option.
When the setting method is the same as that of
the operation block, check that " The same as that
of the block for operation " is selected, and proceed
to step 6).
“The same as that of the block for operation”:
The charging block is the same as the operation
block.
“Create separately”:
Set the charging blocks separately.
Note:
Each capacity column for all the indoor units is indicated in light blue as an item required for setting.
Enter the operating capacity and FAN capacity and auxiliary heater capacity.
(For indoor units without auxiliary heaters, set the auxiliary heater to “0W”.)
When the model name of the indoor unit for which the model name is set in section “8.7.2 Model
Name” corresponds to the internal data, the parameter is displayed automatically. Check the
displayed value and correct it, as required.
The units not included in the charge apportioning billing should be set to “0W.”
Each parameter differs depending on the machine model. Please see the data book or catalog fo
r
details.
A warning message appears if even one indoor unit does not have its parameter set. Make sure
each parameter is set to proceed.
Note that the proportional division may fail to be calculated correctly unless the parameter of all
indoor units (intended for proportionally divided power charge) is set properly.
When the Indoor Unit Division Mode is set to “Do not”, set the indoor unit parameter of “Cooling
Capacity” and “Power input (Cooling)”.
For Without WHM connection proportionally divided electric charge (manual input of the electric
amount), set the indoor unit parameter of “Cooling Capacity”, “Power input (Cooling)” and “
A
uxiliar
y
heater”.
Indoor Unit Settings screen
Indoor unit parameter
set column
Select AG-150A/G-50A
Charg
e
Block Setting screen
Charge block set
- u
p
Operation
bloc
k
Charge block
Charge block name
Ob
j
ect bloc
k
OA processing unit