8.9.4 Function setting (Step 3)
Setting the PLC function
[Procedure]
1) Set the function.
Select the function to be used with each PLC.
2) Select the [OK] after making the setting.
* When interlocking control is performed,
“Air-conditioner state monitoring function”
must be set to “Activate”.
8.9.5 Advanced setting (air conditioner status monitor setting) (Step 4)
Setting the AG-150A/G-50A for air conditioner status
monitor
[Procedure]
1) Select the PLC No.
Select the PLC No. by clicking the “
” button.
2) Select the AG-150A/G-50A No. to be monitored.
Select the No. of the AG-150A./G-50A to be monitored
by each PLC.
* If a PLC for which air conditioner status monitor is
not selected in Step 3, the message "This function
cannot be used." will appear. To use this function,
return to the previous screen and set the functions
again.
8.9.6 Advanced setting (Peak cut function setting) (Step 5)
Set the AG-150A/G-50A for peak cut operations
[Procedure]
1) Select the PLC No.
Select the PLC No. by clicking the “
” button.
2) Select the AG-150A/G-50A No. to be monitored.
Select the AG-150A/G-50A for peak cut operation with
each PLC.
* If a PLC for which peak cut is not selected in Step 3,
the message "This function cannot be used." will
appear. To use this function, return to the Step 3 and
set the functions again.
Note:
• To enable the interlock control, AG-150A/G-50A to be
monitored must be set even if a PLC is not interlocked
with an air-conditioner.
Note:
• With this screen, the equipment for which the peak
cut function is enabled by connecting a demand
controller to the PLC for general equipment is set.
Set the control details of the peak cut function with
the energy saving/peak cut settings in section 8.17.
Note:
• The air conditioner status monitor function and
peak cut function cannot be set for the same
PLC.
Similarly, the general equipment status monito
r
function and peak cut function cannot be set fo
r
the same PLC.
• “Air-conditioner state monitoring function”
includes the monitoring function of the general
equipment connected to the indoor unit free
contact points, and the interlock control function.
When checking the set value for PLC,
press the monitor button.