11. OPTIONS AND PERIPHERAL EQUIPMENT
11 - 91
11.16 EMC filter (recommended)
It is recommended that one of the following filters be used to comply with EN EMC directive. Some EMC
filters have large in leakage current. When using an EMC filter, always use one for each servo amplifier.
(1) Combination with the servo amplifier
Servo amplifier
Recommended filter (Soshin Electric)
Mass
[kg]
Model Rated current [A]
Rated voltage
[VAC]
Leakage current
[mA]
MR-J4-10B(-RJ) to
MR-J4-100B(-RJ)
(Note)
HF3010A-UN
10
250
5
3.5
MR-J4-200B(-RJ)
MR-J4-350B(-RJ)
(Note)
HF3010A-UN
30 5.5
MR-J4-500B(-RJ)
MR-J4-700B(-RJ)
(Note)
HF3040A-UN
40
6.5
6
MR-J4-11KB(-RJ)
MR-J4-15KB(-RJ)
MR-J4-22KB(-RJ)
(Note)
HF3100A-UN
100 12
MR-J4-60B4(-RJ)
MR-J4-100B4(-RJ)
TF3005C-TX 5
6
MR-J4-200B4(-RJ) to
MR-J4-700B4(-RJ)
TF3020C-TX 20
500 5.5
MR-J4-11KB4(-RJ) TF3030C-TX 30 7.5
MR-J4-15KB4(-RJ) TF3040C-TX 40
12.5
MR-J4-22KB4(-RJ) TF3060C-TX 60
MR-J4-10B1(-RJ) to
MR-J4-40B1(-RJ)
(Note)
HF3010A-UN
10 250 5 3.5
Note.
A
surge protector is separately required to use any of these EMC filters.
(2) Connection example
(a) 200 V class/100 V class
MCCB
L1
L2
L3
L11
L21
Servo amplifier
1
2
3
4
5
6
E
(Note 2)
Surge protector
(RSPD-250-U4)
(OKAYA Electric Industries Co., Ltd.)
(Note 1)
Power supply
123
MC
EMC filter
Note 1. Refer to section 1.3 for the power supply specifications.
2. The example is when a surge protector is connected.