Bosch Appliances 3.5 Home Security System User Manual


 
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | ISO7240-16: 2007 en | 69
Excluded clauses
Clause / Requirement Compliance Signature
EN54-16, clause 12.1 Emergency microphone - option
with requirements.
c Where a pre-announcement attention drawing signal is
provided, an indicator adjacent to the microphone shall
show when the signal has finished and live speech can
commence.
This clause is not part of ISO7240-16.
Clause / Requirement Compliance Signature
EN54-16, clause 13.4.1 Electrical and other design
requirements
The processing of signals shall give the highest priority to
the voice alarm condition.
This clause is not part of ISO7240-16.
EN54-16, clause 13.13 Message store(s)
Pre-recorded messages shall be stored in non-volatile
memory that retains the messages when all power sources
are removed.
NOTE The use of tapes or magnetic or optical data disks
for the storage of emergency messages is not acceptable
at the time of drafting this European Standard
(see Annex C)
The NOTE is not part of ISO7240-16.