Bosch Appliances 3.5 Home Security System User Manual


 
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | EN54-16: 2008 en | 45
Clause / Requirement Compliance Signature
13 Design requirements
13.1 General requirements and manufacturer's
declarations
Praesideo is compliant.
13.1.1 The VACIE shall comply with the design
requirements of this clause, where relevant to the
technology used. Some requirements can be verified by
testing. Others can only be verified by inspection of the
design and its accompanying documentation because of
the impracticability of testing all of the possible
combinations of functions and of establishing the long-term
reliability of the VACIE.
See the relevant clauses regarding testing and
documentation.
13.1.2 In order to assist the process of design inspection,
the manufacturer shall declare the following in writing:
a that the design has been carried out in accordance with
a quality management system which incorporates a set
of rules for the design of all elements of the VACIE;
The Bosch Security Systems development department
responsible for development/maintenance of the Praesideo
system works according its own development process,
Standard Development Process or SDP, that is created
using the CMMI model. The SDP implements all process
areas at maturity level 2 of the CMMI model, and some
process areas at maturity level 3 of the CMMI model.
Rules for the design of all elements of the Praesideo
system can be found in the SDP repository. In the SDP
repository all process descriptions, process
implementation documents, templates, guidelines, etc. of
the development processes can be found.
The SDP repository is a version control system.
b that the components of the VACIE have been selected
for the intended purpose and are expected to operate
within their specification when the environmental
conditions outside the cabinet of the VACIE comply
with Class 3k5 of EN 60721-3-3:1995 + A2:1997.
The components of the Praesideo system operate within
their specification within the specified environmental
conditions (Class 3k5 of EN 60721-3-3:1995 + A2:1997).
This is verified by means of testing and is documented in
the test reports. The 19"-racks for Praesideo are part of the
system and subject to certification. A rack must be selected
from the list of approved racks for this purpose.
13.2 Documentation Praesideo is compliant.
13.2.1 The manufacturer shall prepare installation and user
documentation which shall be submitted to the testing
authority together with the VACIE. This shall comprise at
least the following:
The Praesideo Installation and User Instructions (IUI) are
provided as multilingual pdf-files on the DVD that contains
the software for installation and configuration. The IUI can
also be downloaded from Extranet.
a a general description of the equipment, including a list
of
The IUI contains a general description of the Praesideo
system. It includes an EN54-16 checklist, containing a list
of supported optional functions.
It describes all Praesideo functions related to EN54-16 or
otherwise.
1 the optional functions with requirements of this
European Standard,
See this checklist, clause 4.1.1.
2 the functions relating to other parts of EN 54, and
3 the ancillary functions not required by this
European Standard;
b technical specifications of the inputs and outputs of the
VACIE, sufficient to permit an assessment of the
mechanical, electrical, and software compatibility with
other components of the system (e.g. as described in
EN 54-1), including where relevant
The inputs and outputs for audio and control are described
in the IUI, including the technical data, system functions,
configuration instructions, compliancy to standards. This
includes the information as requested in 13.2.1 b) 1)..7).
The Open Interface is described in the ‘Open Interface
Programming Instructions’ (OIPI). This document is always
delivered together with the Praesideo system as a pdf-file
on the distribution DVD. This document gives enough
information for third party programmers to create
applications to control or display Praesideo functions.
1 the power requirements for recommended
operation,
2 the maximum number of voice alarm zones,
3 information concerning the connection of
emergency microphones,
4 the maximum and minimum electrical ratings for
each input and output,