Praesideo 3.5 | Installation and User Instructions | 9 | System Configuration en | 400
Class-A switchover
Group A fault
Group A or B line fault
Group B fault
Incompatible hardware version
Pilot tone calibration failure
Unit missing
Loudspeaker faults are excluded from the list of zone
related faults that will activate the zone fault indicator,
so loudspeaker end-of-line supervision must be used
instead or additionaly to comply to EN54-16. This is
because in Praesideo loudspeaker faults are not assigned
to a specific amplifier output or zone, but only to the
loudspeaker itself, wherever it is.
It is also possible to configure this Zone status function on
an LBB4432/00 keypad, but then the second LED will
turn on for the active priority call, which is yellow. For a
zone fault the first LED will flash, which is green. In
most cases these colors are not acceptable, so better use
an LBB4434/00 with dedicated indicators. Also, on an
LBB4432/00 keypad these indicators cannot be
combined with the Zone selection key, which has its own
bi-color indicator. On a custom panel, using the
LBB4434/00 keypad kits, the indicators and switch of a
Zone selection key and the Zone status indicators can be
grouped together to give a clear overview of the
selection.
Priority - The action is activated if the priority is
equal to or higher than this specified priority.
Available outputs - Shows the available zones,
zone groups and control outputs. Use the dropdown
list to choose the type of outputs that are shown.
Add/Remove buttons - Using the > and <
buttons, selected outputs can be added to or
removed from Assigned outputs.
Assigned outputs - Shows the outputs that have
been assigned to the key.
47.3.33 Zone priority status
The Zone priority status action is intended for
LBB4434/00 Call Station Keypad Kits. The key/input
itself is not used by this action; only the indicator/output
attached to the key is activated. The Zone priority status
action activates the indicator/output belonging to the
key if there is a call made to the zone with a priority
equal to the defined priority. The purpose of this
function is to be able to build a custom display with
zone indicators that will show in which zones a call with
a specific priority is busy. In this way the indicators can
show whether a certain emergency or alert message is
running in a zone by setting the defined priority to the
priority of that message.
See figure 47.39 for an overview of the Action
programming page for a Zone priority status key.
Configuring a Zone priority status key is similar to
configuring a Zone status key (see section 47.3.32).
figure 47.38: Zone status key
figure 47.39: Zone priority status key