Bosch Appliances 3.5 Home Security System User Manual


 
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | 10 | Events en | 428
Event message:
Messages missing
Originator:
Unit in which the fault occurred.
Extra information:
Name(s) of message(s) that are present in the
configuration, but are not present on the flash card.
Description:
Logs the mismatch of the configured and detected
messages in the flashcard. Can only occur when the
availability of a flash card is enabled with the
configuration software and restart the network
controller.
Resolve:
When the fault disappears.
Recommended action:
Check the file names. (These are case-sensitive.) If
the message names appear to be correctly
configured, upload the message set again and restart
the network controller.
Event message:
Microphone failure
Originator:
Audio input in which the fault occurred.
Extra information:
This fault event can only be generated by call stations
and power amplifiers.
Description:
Logs the failure of a microphone on or connected to a
unit.
Resolve:
When the fault disappears or when the unit
disconnects.
Recommended action:
Check the microphone and its connections to the
system. If necessary, repair them.
Event message:
Network power supply failure remote call station
Originator:
Remote call station that detects the network power
supply failure.
Extra information:
----
Description:
Logs a failure of the network power supply of a remote
call station.
Resolve:
When the call station interface disconnects or when
the fault is no longer present.
Recommended action:
Connect the network power supply or disable the
network power supervision in the configuration.