Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | EN54-16: 2008 en | 28
Clause / Requirement Compliance Signature
5 General requirements for indications
5.1 Display and functional conditions Praesideo is compliant.
5.1.1 The VACIE shall be capable of unambiguously
indicating the following functional conditions, as described
in Clauses 6 to 9:
• quiescent condition;
• voice alarm condition;
• fault warning condition;
• disablement condition (option with requirements)
See Clauses 6 to 9.
5.1.2 The VACIE shall be capable of being simultaneously
in any combination of the following functional conditions on
different voice alarm zones:
The Praesideo system is capable of being simultaneously in
the voice alarm condition and in the fault warning condition.
• voice alarm condition; The voice alarm condition is indicated per system on each
call station (system status LED) and on the display of the
network controller (emergency menu). This system wide
indication can be combined with the indication of the fault
warning condition: each call station uses a different LED
(power/fault LED) for indication of the fault warning
condition; therefore both conditions can be indicated
simultaneously. The display of the network controller can
indicate both the voice alarm condition and the fault
warning condition (note that it will only show one condition
automatically, the voice alarm condition has precedence;
the user is able to see the fault warning condition by
navigating through the menu if both conditions apply to the
system simultaneously).
To indicate the voice alarm condition per zone, the installer
shall use a call station keypad kit with correctly connected
red LEDs (see clause 13.9.1) with configuration of the
‘Zone status’.
• fault warning condition; The fault warning condition is indicated per system on each
call station (power/fault LED) and on the display of the
network controller (faults menu). This system wide
indication can be combined with the indication of the voice
alarm condition: each call station uses a different LED
(system status LED) for indication of the voice alarm
condition; therefore both conditions can be indicated
simultaneously. The display of the network controller can
indicate both the voice alarm condition and the fault
warning condition (note that it will only show one condition
automatically, the voice alarm condition has precedence;
the user is able to see the fault warning condition by
navigating through the menu if the system is in both
conditions simultaneously).
The installer must configure zone names in a way that the
zone name is visible in the fault logging and network
controller display (see clause 8.2.7 for details). In this way
faults are indicated per zone.
• disablement condition (option with requirements). The optional disablement condition is not implemented in
Praesideo.
5.2 Indication display Praesideo is compliant.
All mandatory indications shall be clearly identifiable, except
where otherwise specified in this European Standard.
The Praesideo system uses the following color coding for
indications throughout the system:
• Green: system ok
• Red: system/zone in voice alarm condition
• Yellow: system in fault warning condition