Praesideo 3.5 | Installation and User Instructions | 9 | System Configuration en | 389
47.3.5 Start
The Start action is intended for making emergency calls
for phased evacuation. The Start action starts a call,
based on a call macro, in a pre-defined zone or zone
group. The priority of the call is the same as the priority
of the call macro and cannot be changed. See figure
47.12 for an overview of the Action programming page for
a Start key.
If more than one action (up to a maximum of 5) is
configured for a Start key or control input, see section
43.2.5, then also multiple sets of Call macro and Zones
can be configured here.
Typically, there will be multiple Start actions that use
the same call macro, but address other zones or zone
groups. In case of a phased evacuation, the different
Start actions then can be used to expand the area in
which the call is running.
When the activator of a Start action is released, the
running call is stopped in the zones or zone groups that
are associated to the action. In case of a phased
evacuation, releasing the different Start actions can be
used to reduce the area in which the call is running.
47.3.6 Stop
The Stop action is intended for aborting emergency calls
for phased evacuation. The Stop action aborts all calls
that are based on the defined call macro. See figure
47.13 for an overview of the Action programming page for
a Stop key.
If more than one action (up to a maximum of 5) is
configured for a Stop key or control input, see section
43.2.5, then also multiple Call macros can be configured
here.