Praesideo 3.5 | Installation and User Instructions | 9 | System Configuration en | 344
43.2.6 Control outputs
figure 43.8: Configure network controller, step 6
table 43.5: Control outputs configuration
Item Value Description
Output
Unique name for the control output. The output can be enabled and
disabled using the checkbox.
Mains power fault grace
time
0 h (default),
1 h, 2 h,
3 h ...8 h
Selects whether control output 5 with the fixed function Fault alarm
indicator acts immediately on the occurrence of a mains power fault, or
that activation is suspended and will only happen if the mains power
fault is still present after the configured grace time. All other faults will
result in an immediate activation of this
Fault alarm indicator. The
purpose of the grace time is to suspend a warning to an external
service center for systems in areas where short mains failures
frequently happen. The system backup power supply should at least
be able to provide power during the configured grace time. The
Fault
alarm buzzer is not delayed in order to give a local warning immediately.
Function
Sets the purpose of the control output. See table 43.6.