Bosch Appliances 3.5 Home Security System User Manual


 
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | 9 | System Configuration en | 355
43.4.4 General (PRS-CSR and
PRS-CSRK)
figure 43.24: Configure call station, step 1
table 43.12: General configuration settings (PRS-CSR)
Item Value Description
Class Normal
Emergency
Sets the priority range of the call station. This is either Normal
for 32 to 223 or Emergency for 32 to 255. When Class is
Emergency the call station can make fail-safe calls.
Clear selection after call Ye s
No
Selects whether selections that are made on a keypad for a call
(zone selection, priority selection, tone selection and message
selection) will be cleared after the call has finished or will be
kept for a next call.
Remote call station
supervision
On
Off
Selects whether the remote call station and its connection to
the call station interface will be supervised or not. If set to No, it
is possible to disconnect and remove the remote call station
without generating a fault in the system. This can be
convenient for call stations that would otherwise remain
unattended. Emergency call stations should always be
supervised.
Remote call station
network power
supervision
On
Off
When Remote call station network power supervision is On
and the network power connection between the remote call
station interface and the remote call station is failing, a fault
event is generated.
Remote call station
back-up power
supervision
On
Off
When Remote call station back-up power supervision is On
and the external power supply that is connected to the remote
call station is failing, a fault event is generated.
Call station interface
network power
supervision
On
Off
When Call station interface network power supervision is On
and the network power connection between the call station
interface and the Praesideo network is failing, a fault event is
generated.
Call station interface
back-up power
supervision
On
Off
When Call station interface back-up power supervision is On
and the external power supply that is connected to the call
station interface is failing, a fault event is generated.