Praesideo 3.5 | Installation and User Instructions | 9 | System Configuration en | 345
table 43.6: Control output types
Function Description
Switch output The control output is activated by a Switch trigger control input or keypad key. See
section 47.3.27.
Zone active output The control output is activated when there is an active call in the associated zone (see
section 45.2.
Volume override output The control output is activated when there is an active call with priority 32 or higher in
the associated zone. See section 45.2.
Fault alarm buzzer The control output activates a fault alarm buzzer (e.g a connected buzzer) each time a
fault is detected in the system. It can only be deactivated by acknowledging all faults.
Fault alarm indicator The control output activates a visual fault indicator (e.g. a lamp) each time a fault is
detected in the system. It can only be deactivated by resetting all faults.
System fault indicator The control output activates a visual fault indicator (e.g. a lamp), each time a System
fault is detected in the system. System faults are a special category of faults, a subset
of all possible faults. System faults are: Configuration file error, Flash card data error,
Flash card missing, No valid configuration file found, Processor reset.
Emergency alarm buzzer The control output activates an emergency alarm buzzer (e.g a connected buzzer) each
time a call with priority 223 or higher is started (i.e. an emergency call). It can only be
deactivated by acknowledging the emergency state.
Emergency alarm
indicator
The control output activates a visual emergency indicator (e.g. a lamp) each time a call
with priority 223 or higher is started (i.e. an emergency call). It can only be deactivated
by resetting the emergency state.