Bosch Appliances 3.5 Home Security System User Manual


 
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | EN60849: 1998 en | 24
EN60849 - 7. Instructions for use
EN60849 - 7.1 Instructions for operation
EN60849 - 7.2 Records to be kept
Requirement Compliance Signature
Instructions for the operation of the system, including
actions to be taken in accordance with established and
well-rehearsed procedures, shall be available for rapid
reference, preferably prominently and permanently
displayed, at each control station.
Responsibility of the installer.
As far as possible, graphic illustrations should be used:
where text is necessary this should be clearly legible
and in the preferred language(s).
Responsibility of the installer.
Updating of the instructions for operation shall be
carried out after additions to or modifications of the
system, or on the basis of practical experience, or
revised procedures.
Responsibility of the installer.
Instructions shall include:
The functional operation of the system. Responsibility of the installer.
Action to be taken in the event of a system failure. Responsibility of the installer.
A bound copy of the operational instructions shall be
provided.
Responsibility of the installer.
Requirement Compliance Signature
Installation, logbook and maintenance records shall be
kept by the end-user and/or maintenance company
contracted by the end-user in accordance with relevant
international and national standards. These shall
comprise as a minimum:
a Installation Responsibility of the installer.
1 details of the locations of all items of the
equipment.
Responsibility of the installer.
2 “as installed” performance measurements of
the system including:
Responsibility of the installer.
•measured loudspeaker loading per circuit in
emergency mode.
Responsibility of the installer.
•settings of any adjustable items within the
system, including the output level of power
amplifiers.
Responsibility of the installer.
•sound pressure levels. Responsibility of the installer.
•intelligibility measurements. Responsibility of the installer.
b Log book
A stiff covered log book shall be kept, in which all
usage of the system and all fault occurrences
should be recorded, together with all available
automatically produced records, to include:
Responsibility of the person nominated by the person or
body, having control of the premises (see 4.2). Action
to be taken care of by the installer.
1 dates and times of usage of the system.
2 details of tests and routine checks carried out.
3 time and date of each fault occurrence.
4 details of the fault found and the circumstances
of it being found (for example during routine
maintenance).
5 action taken to rectify or remedy.
6 date, time and name of person in charge of the
system.
7 countersignature of the responsible person, if
any faults occurred or have been rectified.