Bosch Appliances 3.5 Home Security System User Manual


 
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | 4 | Amplifiers en | 187
The loudspeakers listed in table 11.2 have a provision
for a supervision-slave.
11.4 Technical data
supervision-master
11.4.1 Physical characteristics
11.4.2 Climate conditions
11.4.3 EMC and Safety
11.4.4 Mean time between failure
table 11.2: Loudspeakers that have provision for a
supervision-slave
Speaker type Provision for
mounting
Pre-wired, no
provision for
mounting
Ceiling speakers
LC1-WM06E
LC1-UM06E
LC1-UM12E
LC1-UM24E
LB C 3 510/40
LBC 3520/40
LBC 3530/40
9
9
9
9
9
9
9
Cabinets
LBC 3011/41
LBC 3011/51
LB1-UM06E
LBC 3018/00
9
9
9
9
Columns
LB C 3210 /00
LA1-UM20E
LA1-UM40E
9
9
9
Horns/Drivers
LBC 3403/16
LBC 3404/16
LBC 3405/16
LBC 3406/16
LH1-10M10E
LBC 3482/00
LBC 3483/00
LBC 3484/00
9
9
9
9
9
9
9
9
Sound projectors
LP1-BC10E
LP1-UC10E
LP1-UC20E
LBC 3432/01
LS1-OC100E
9
9
9
9
9
Note
The installer shall only use EN54-24 compliant
loudspeakers for emergency sound systems in
Europe.
Dimensions (H x W x D):
60 x 50 x 17 mm
Weight:
30 g
Connection:
20 pole flatband cable and connector
Installation:
Plastic brackets for horizontal or vertical installation
are delivered with the amplifier.
Temp era tur e:
-5 to 55 °C (operating)
-20 to 70 °C (non-operating)
Relative humidity:
15 to 90%, non-condensing (operating)
5 to 95%, non-condensing (non-operating)
Air pressure:
600 to 1100 hPa
Electromagnetic compatibility:
E N55103-1/ FCC -47 part 15B
E N55103-2
EN50121-4
EN50130-4
Electrical safety:
IEC60065 (CB-scheme)
EN60065
Approvals:
CE marking
EN60849, EN54-16 and ISO7240-16
IEC60945
MTBF:
50,000 hours at +55 °C
(The MTBF doubles for every 10 °C decrease in
temperature.)