Emerson Process Management HASX2E-IM-HS Carbon Monoxide Alarm User Manual


 
Emerson Process Management GmbH & Co. OHG 2-7
X-STREAM X2
Instruction Manual
HASX2E-IM-HS
02/2012
2
Technical data
2.2.1 Model-Specic Technical Data: X-STREAM X2GK
Housing
admissible operational ambient temperature: 0 °C to +50 °C (32 to 122 °F)
admissible ambient temperature for storage: -20 °C to +70 °C (-4 to 158 °F)
weight approx. 8–12 kg (17.6–26.4 lb)
(dependent on conguration)
EN 60529 housing protection type: IP 20 for indoor use.
Units must be protected against dripping
water and splashes, and direct sunlight.
Gas connections: quantity: max. 6
of which optional: 1 or 2 for purge gas
material: PVDF 6/4 mm
optionally stainless steel 6/4 mm or 1/4",
other options on request
Power Supply
Instrument data
Nominal input voltage 24 V
100–240 V 50/60 Hz
Input voltage range 10–30 V 85–264 V, 47–63 Hz
Nominal input current 2.5 A max. 1.3–0.7 A max.
Connection via 3-pin
XLR connector on
rear panel
Connection via IEC
appliance on rear pa-
nel
Power Input fuse
Data for fuse link:
AC 230 V / T 3.15 A /
5x20 mm
AC 230 V / T 4 A /
5x20 mm
Signal inputs and outputs
As standard, signal cables are connected using Submin-D plugs or sockets on the unit’s rear
panel (except Ethernet: RJ45 socket) (
Fig. 2-2)
Detailed terminal conguration
4.4.1 Installation, page 4-7.