Setup.Display.Language 3162 3162 Word R/W
LOI‘s language (0=EN, 1=DE, 2=3rd
language)
Setup.Display.LOIAutoHome 3163 3163 Word R/W
Auto ‚Home‘ for LOI (0=Never, 1=1mi-
nute, 2=10minutes)
Setup.Display.MeasureLines.MeasLine1 3166 3166 Word R/W
signal assigned to line1 of 1st mea-
surement display(0..n)
Setup.Display.MeasureLines.MeasLine2 3167 3167 Word R/W
signal assigned to line2 of 1st mea-
surement display(0..n)
Setup.Display.MeasureLines.MeasLine3 3168 3168 Word R/W
signal assigned to line3 of 1st mea-
surement display(0..n)
Setup.Display.MeasureLines.MeasLine4 3169 3169 Word R/W
signal assigned to line4 of 1st mea-
surement display(0..n)
Setup.Display.MeasureLines.MeasLine5 3313 3313 Word R/W
signal assigned to line1 of 2nd mea-
surement display(0..n)
Setup.Display.MeasureLines.MeasLine6 3314 3314 Word R/W
signal assigned to line2 of 2nd mea-
surement display(0..n)
Setup.Display.MeasureLines.MeasLine7 3315 3315 Word R/W
signal assigned to line3 of 2nd mea-
surement display(0..n)
Setup.Display.MeasureLines.MeasLine8 3316 3316 Word R/W
signal assigned to line4 of 2nd mea-
surement display(0..n)
Setup.Display.MenuAccesss.AutoCodeMode 3170 3170 Word R/W
denes how codes autom. locked
(0=never,1=home,2=1minute)
Setup.Display.MenuAccesss.BasicAccess-
Code
3171…
3174
3171…
3174
String R/W
user code for getting access to basic
areas
Setup.Display.MenuAccesss.BasicAccMode 3175 3175 Word R/W
mode for access to basic areas
(0=allowed,1=code, 2=prohibited)
Setup.Display.MenuAccesss.ExpertAccess-
Code
3176…
3179
3176…
3179
String R/W
user code for getting access to expert
areas
Setup.Display.MenuAccesss.ExpertAccMode 3180 3180 Word R/W
mode for access to expert areas (0=all
owed,1=code,2=prohibited)
Setup.Display.MenuAccesss.SpecialAcces-
sCode
3181…
3184
3181…
3184
String R/W
user code for getting access to special
areas
Setup.Display.MenuAccesss.SpecialAccMo-
de
3185 3185 Word R/W
mode for access special areas (0=allow
ed,1=code,2=prohibited)
Setup.Display.SecVars.FlowDecimalPoint 3150 3150 Word R/W decimal point position for ow displays
Setup.Display.SecVars.FlowUnit 3149 3149 Word R/W unit to display ows (0=??, 1=??)
Setup.Display.SecVars.PresDecimalPoint 3140 3140 Word R/W
decimal point position for pressure
displays
Setup.Display.SecVars.PressUnit 3139 3139 Word R/W
unit to display pressures (0=Pa,1=hPa,
2=mbar,3=Bar,4=psig)
Setup.Display.SecVars.TempDecimalPoint 3130 3130 Word R/W
decimal point position for temperature
displays