9.3 List of Parameters and Registers - Sorted by Tag Name
Tag Name
Address
Data
Type
Client
Access
Description
Modicon Daniel
Setup.Display.SecVars.TempUnit 3129 3129 Word R/W
unit to display temperatures (0=°C,
1=°F)
Setup.In/Outputs.AnalogOut.AOutEndRan-
ge1
6093…
6094
9047 Float R/W
level (ppm) where analoge output sca-
ling ends for comp1
Setup.In/Outputs.AnalogOut.AOutEndRan-
ge2
6095…
6096
9048 Float R/W
level (ppm) where analoge output sca-
ling ends for comp2
Setup.In/Outputs.AnalogOut.AOutEndRan-
ge3
6097…
6098
9049 Float R/W
level (ppm) where analoge output sca-
ling ends for comp3
Setup.In/Outputs.AnalogOut.AOutEndRan-
ge4
6099…
6100
9050 Float R/W
level (ppm) where analoge output sca-
ling ends for comp4
Setup.In/Outputs.AnalogOut.AOutSignalAs-
sign1
3017 3017 Word R/W
asgn AOut1(0=std,1=AdjStart,2=AdjEn
d, 3=Rng-C2)
Setup.In/Outputs.AnalogOut.AOutSignalAs-
sign2
3018 3018 Word R/W
asgn AOut2
(0=std,1=AdjStart,2=AdjEnd, 3=Rng-
C2)
Setup.In/Outputs.AnalogOut.AOutSignalAs-
sign3
3019 3019 Word R/W
asgn AOut3
(0=std,1=AdjStart,2=AdjEnd, 3=Rng-
C2)
Setup.In/Outputs.AnalogOut.AOutSignalAs-
sign4
3020 3020 Word R/W
asgn AOut4
(0=std,1=AdjStart,2=AdjEnd, 3=Rng-
C2)
Setup.In/Outputs.AnalogOut.AOutStar-
tRange1
6085…
6086
9043 Float R/W
level (ppm) where analoge output sca-
ling starts for comp1
Setup.In/Outputs.AnalogOut.AOutStar-
tRange2
6087…
6088
9044 Float R/W
level (ppm) where analoge output sca-
ling starts for comp2
Setup.In/Outputs.AnalogOut.AOutStar-
tRange3
6089…
6090
9045 Float R/W
level (ppm) where analoge output sca-
ling starts for comp3
Setup.In/Outputs.AnalogOut.AOutStar-
tRange4
6091…
6092
9046 Float R/W
level (ppm) where analoge output sca-
ling starts for comp4
Setup.In/Outputs.AnalogOut.AOutType 3016 3016 Word R/W
AOut behavior (0=0_20,1=4_20,2=0_2
0L,3=4_20L,4=0_20H,5=4_20H)
Setup.In/Outputs.AnalogOut.Zoom1 3261 3261 Word R/W Zoom AOut1 (in %)
Setup.In/Outputs.AnalogOut.Zoom2 3262 3262 Word R/W Zoom AOut2 (in %)
Setup.In/Outputs.AnalogOut.Zoom3 3263 3263 Word R/W Zoom AOut3 (in %)
Setup.In/Outputs.AnalogOut.Zoom4 3264 3264 Word R/W Zoom AOut4 (in %)
Setup.In/Outputs.AnalogOut.ZoomControl1 3265 3265 Word R/W
ZoomControl of AOut1 (0=Manual,
1=DigInput, 2=Auto)
Setup.In/Outputs.AnalogOut.ZoomControl2 3266 3266 Word R/W
ZoomControl of AOut2 (0=Manual,
1=DigInput, 2=Auto)
Setup.In/Outputs.AnalogOut.ZoomControl3 3267 3267 Word R/W
ZoomControl of AOut3 (0=Manual,
1=DigInput, 2=Auto)
Setup.In/Outputs.AnalogOut.ZoomControl4 3268 3268 Word R/W
ZoomControl of AOut4 (0=Manual,
1=DigInput, 2=Auto)