3. SIGNALS AND WIRING
(3) MR-J3-10A1 to MR-J3-40A1
P
N
(Note 4)
Trouble
SON
EMG
L
1
Blank
L2
1-phase
100 to
120VAC
ALM
P
1
P
2
DICOM
DOCOM
L11
L21
D
C
U
V
W
(Note 1)
(Note 2)
CNP1
CNP3
PE
CNP2
U
V
W
M
Motor
Encoder
CN2
(Note 3)
Encoder cable
(Note 5)
DOCOM
CN1 CN1
24VDC
Trouble
(Note 4)
MCNFB
RA
Servo motorServo amplifier
Emergency stop (Note 6)
Servo-on
RA
Emergency stop
OFF
MC
ON
MC
SK
(Note 6)
(Note 7)
Note 1. Always connect P1 and P2. (Factory-wired.) The power factor improving DC reactor cannot be used.
2. Always connect P and D. (Factory-wired.) When using the regenerative option, refer to section 12.2.
3. For encoder cable, use of the option cable is recommended. Refer to section 12.1 for selection of the cable.
4. For the sink I/O interface. For the source I/O interface, refer to section 3.8.3.
5. Refer to section 3.10.
6. Configure the circuit to shut down the main circuit power supply simultaneously with the turn off of emergency
stop (EMG) using the external sequence.
7. Be sure to use a magnetic contactor with an operation delay time of 80ms or less. The operation delay time is
the time interval between current being applied to the coil until closure of contacts.