12 - 81
12. OPTIONS AND AUXILIARY EQUIPMENT
Note 1. d is as shown below.
d
Conductor
Insulation sheath
2. Purchase from Toa Electric Industry
3. Standard OD. Max. OD is about 10
greater.
4. Purchase from Taisei
5. Taiyo Electric Wire and Cable
6. These wire sizes assume that the UL-compliant wires are used at the wiring length of 10m.
7. These models consist with solid wires. Specify the color, separately.
12.12 No-fuse breakers, fuses, magnetic contactors
Always use one no-fuse breaker and one magnetic contactor with one servo amplifier. When using a fuse
instead of the no-fuse breaker, use the one having the specifications given in this section.
Servo amplifier
No-fuse breaker Fuse
(Note 2)
Magnetic
contactor
Current
Voltage
AC
(Note 1)
Class
Current
[A]
Voltage
AC
[V]
Not using power
factor improving
reactor
Using power factor
improving reactor
MR-J3-10A(1) 30A frame 5A 30A frame 5A 10
S-N10
MR-J3-20A 30A frame 5A 30A frame 5A 10
MR-J3-20A1 30A frame 10A 30A frame 10A 15
MR-J3-40A 30A frame 10A 30A frame 5A 15
MR-J3-60A
MR-J3-70A
MR-J3-100A
MR-J3-40A1
30A frame 15A 30A frame 10A
240V
20
300
MR-J3-200A 30A frame 20A 30A frame 15A 40 S-N18
MR-J3-350A 30A frame 30A 30A frame 30A 70 S-N20
MR-J3-500A 50A frame 50A 50A frame 40A 125 S-N35
MR-J3-700A 100A frame 75A 50A frame 50A
T
150 S-N50
MR-J3-11KA 100A frame 100A 100A frame 75A 200 S-N65
MR-J3-15KA 225A frame 125A 100A frame 100A 250 S-N95
MR-J3-22KA 225A frame 175A 225A frame 150A 350 S-N125
MR-J3-60A4 30A frame 5A 30A frame 5A 10
MR-J3-100A4 30A frame 10A 30A frame 10A 15 S-N10
MR-J3-200A4 30A frame 15A 30A frame 15A 25
MR-J3-350A4 30A frame 20A 30A frame 20A 35
S-N18
MR-J3-500A4 30A frame 30A 30A frame 30A 600Y/347V 50 600
MR-J3-700A4 50A frame 40A 50A frame 30A 65 S-N20
MR-J3-11KA4 60A frame 60A 50A frame 50A 100 S-N25
MR-J3-15KA4 100A frame 75A 60A frame 60A 150 S-N35
MR-J3-22KA4 225A frame 125A 100A frame 100A 175 S-N65
Note 1. When not using the servo amplifier as a UL/CSA Standard compliant product, K5 class fuse can be used.
2. Be sure to use a magnetic contactor with an operation delay time of 80ms or less. The operation delay time is the time interval
between current being applied to the coil until closure of contacts.