SPECIFICATIONS
3.6 Buffer Memory Details
3.6.10 Information linkage function area
3
- 37
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETTINGS AND
PROCEDURE TO
OPERATION
5
INSTALLATION AND
UNINSTALLATION
6
FUNCTIONS
7
MES INTERFACE
FUNCTION
CONFIGURATION TOOL
8
DB CONNECTION
SERVICE AND
SETTING TOOL
3.6.10 Information linkage function area
(1) "Time synchronization" setting status (Buffer memory address: 11500)
(a) The setting status of [Time synchronization setting] is stored.
For [Time synchronization setting], refer to the following.
Section 7.6.2 Setting items in Time synchronization setting
0: [Synchronize with PLC CPU time]
1: [Synchronize with SNTP]
(b) When selecting [Synchronize with SNTP] in [Time synchronization setting]
This area is set when the time information was obtained from the SNTP server
computer.
If the time information could not be obtained from the SNTP server computer, this
area is not set since the operation for when [Synchronize with PLC CPU time] is
selected is performed (Time is synchronized with the programmable controller
CPU).
(2) SNTP time query result (Buffer memory address: 11501 to 11507)
When [Synchronize with SNTP] is selected in [Time synchronization setting], the time
information obtained from the SNTP server is stored.
(When [Daylight saving setting] is enabled, time corrected to daylight saving time is
stored during the period of summer time.)
(3) Monitoring interval timeout count (Buffer memory address: 11510)
The cumulative number of times that a monitoring interval timeout has occurred is
stored.
The monitoring interval timeout occurs when trigger detection has not been completed
within the monitoring interval.
If this timeout occurs, perform the following:
Increase the monitoring interval
Increase the sampling interval of the tag that is used for trigger conditions.
Reduce the trigger detection time.
Reduce the number of configured jobs.
Table 3.19 SNTP time query result
Address
(Decimal)
Name Description Setting side
11501 SNTP time query result (Year) The four-digit year data is stored.
Set on system
side
11502
SNTP time query result
(Month)
The month data, 01 to 12, is stored.
11503 SNTP time query result (Day) The day data, 01 to 31, is stored.
11504 SNTP time query result (Hour) The hour data, 00 to 23, is stored.
11505
SNTP time query result
(Minute)
The minute data, 00 to 59, is stored.
11506
SNTP time query result
(Second)
The second data, 00 to 59, is stored.
11507
SNTP time query result (Day of
the week)
The day of the week data is stored.
0: Sunday 1: Monday 2: Tuesday
3: Wednesday 4: Thursday 5: Friday
6: Saturday