Mitsubishi Electronics QJ7MES96 Thermostat User Manual


 
10
- 16
10.2 Error Code List
10.2.1 Error codes for the MES interface module
10
TROUBLESHOOTING
(From the previous page)
(To the next page)
Table 10.3 Error codes for the MES interface module
Error code Error name Description Action
0B68h
Max. number of acquired
records illegal
The tag component value specified for
the maximum number of acquired
records is 0 or less.
• Set 1 or more to the tag component
value specified for the maximum
number of acquired records.
0B80h System error
• Please consult your local Mitsubishi
representative.
0B81h Communication start error
An error occurred in the Ethernet
communication, and the
communication failed to start.
• Check the Ethernet connection.
• Check if [Server service settings] is
correct.
• Check if the ODBC setting is
correct.
0B82h System error
• Please consult your local Mitsubishi
representative.
0B83h
Communication
connection error
An Ethernet communication error has
occurred.
• Check the Ethernet connection.
• Check if [Server service settings] is
correct.
• Check if the ODBC setting is
correct.
• Check if the server computer has no
problem, referring to the following.
Section 10.1.1 (2) Checking
an error of the server
computer
• Ask your network administrator
about the firewall setting.
Section 5.1 Installation
0B84h
Communication
connection timeout
0B85h
to
0B87h
System error
• Please consult your local Mitsubishi
representative.
0B88h
Message transmission
error
An Ethernet communication error has
occurred.
• Check the Ethernet connection.
• Check if [Server service settings] is
correct.
• Check if the ODBC setting is
correct.
0B89h
Message transmission
timeout
0B8Ah System error
• Please consult your local Mitsubishi
representative.