MES INTERFACE FUNCTION CONFIGURATION TOOL
7.7 Access Target CPU Setting
7.7.1 Setting items in Access target CPU setting
7
- 37
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETTINGS AND
PROCEDURE TO
OPERATION
5
INSTALLATION AND
UNINSTALLATION
6
FUNCTIONS
7
MES INTERFACE
FUNCTION
CONFIGURATION TOOL
8
DB CONNECTION
SERVICE AND
SETTING TOOL
(6) Precautions on [Access target CPU settings]
(a) The MES interface module prepares for communication with the access target
CPU when executing [Update settings], powering ON the system from OFF, or
resetting the programmable controller CPU.
Therefore, if a large number of access target CPUs are set, several minutes are
required for the preparation.
Confirm that [Update settings] is completed, or the MES interface module is ready
(X0 is ON.) before making access from the personal computer to the MES
interface module.
(b) Be sure to set a correct series for [PLC series].
If [PLC series] is incorrectly set, either of the following will occur.
At startup of the MES interface module, an error may occur in a
programmable controller CPU or a module on the route to the access target
CPU.
The system may operate within the device range of the incorrect [PLC series]
setting.
(c) When accessing the Redundant CPU, pay attention to the following points.
When the MES interface module is mounted to the Redundant CPU, it can
access the CPU of host station only.
It cannot access the CPU of other station.
When the MES interface module is mounted to other than the Redundant
CPU, it cannot access the Redundant CPU of other station.