10.2 Error Code List
10.2.1 Error codes for the MES interface module
10
TROUBLESHOOTING
(From the previous page)
(To the next page)
Table 10.3 Error codes for the MES interface module
Error code Error name Description Action
0081h Device type error The specified device type is invalid.
• Correct the device type entered in
[Device tag settings].
0082h Device No. error
The specified device number is out of
range.
• Correct the device number entered
in [Device tag settings].
0083h Device point error
The number of device points is
incorrect.
• Check the CPU(s) on the access
route.
0084h Write size error The write size is not correct.
0085h Link parameter error The link parameter is corrupted.
• Set a correct link parameter for the
programmable controller CPU(s) on
the access route.
0087h
to
0089h
System error
• Please consult your local Mitsubishi
representative.
00D2h RUN time disable error
A request that is not permitted during
RUN was issued.
• Check the CPU(s) on the access
route.
00D4h System error
• Please consult your local Mitsubishi
representative.
00D7h Receive data length error
The receive data length or the byte
length exceeded the limit.
• Check the cables on the access
route.
00D8h Protocol error
The communication protocol is not
correct.
00D9h Address error The address is not correct.
• Check the CPU(s) on the access
route.
00DBh Write error Writing is not executable.
00E0h Station No. error
The specified station number does not
exist.
• Check the station number setting in
[Access target CPU settings].
00E1h Processing mode error
The access target CPU is not capable
of processing the request.
• Check the PLC series in [Access
target CPU settings].
00E2h
Intelligent function module
specification error
The specified intelligent (or special)
function module is faulty.
• Correct the "U \G " buffer
memory data in [Device tag
settings].
00E3h Other data error The request data has an error.
• Check the CPU(s) on the access
route.
00E4h Link specification error
A link module on the access route
received a request that cannot be
handled. (The access route is not
supported.)
• Check the access route referring to
the accessible range.
00E8h System error
• Please consult your local Mitsubishi
representative.
00E9h Link timeout
The access target is disconnected
from the link during the processing.
• Reconnect the access target on the
access route.
00EAh Special module BUSY
The receive buffer of the access target
is full, or is not ready for reception.
• Examine the hardware of the
intelligent (or special) function
module.
00ECh Access target BUSY
The receive buffer of the access target
is full, or is not ready for reception.
• Check the access target.
00F0h Link error
An request was made to a link stop
station.
• Restore the link to connect the
station on the access route.