Mitsubishi Electronics QJ7MES96 Thermostat User Manual


 
10
TROUBLESHOOTING
10.2 Error Code List
10.2.1 Error codes for the MES interface module
10
- 21
9
XML MESSAGE
FORMAT
10
TROUBLESHOOTINGAPPENDICESINDEX
(From the previous page)
(To the next page)
Table 10.3 Error codes for the MES interface module
Error code Error name Description Action
0D00h
Setting file out-of-range
access error
Access was made to outside the
setting file range.
• Turn the power OFF and ON, or
reset the programmable controller
CPU.
0D01h
New setting file creation
error
Failed to create a new setting file.
0D02h Setting file open error Failed to open the setting file.
0D03h Setting file seek error Failed to seek the setting file.
0D04h Setting file read error Failed to read out the setting file.
0D05h Setting file write error Failed to write the setting file.
0D06h Setting file close error Failed to close the setting file.
0D80h
to
0D82h
System error
• Please consult your local Mitsubishi
representative.
100Eh
2000h
to
20FFh
4000h
to
4FFFh
Errors detected by the access target CPU
User's Manual for the access target programmable controller CPU
7000h
to
7FFFh
Errors detected by the serial communication module
User's manual of serial communication module being used
MELSEC-L CPU Module User's Manual (Hardware Design, Maintenance and Inspection)
9000h
System error
• Please consult your local Mitsubishi
representative.
9006h
9008h Send buffer full
There is no available space in the
send buffer.
• Check the control CPU(s) of the
network module(s) on the access
route to the access target CPU
module.
Section 3.2 (2) Accessible
routes
• Check the routing parameter set for
the CPU(s) on the access route.
• Check if the access target PLC
series is supported.
Section 3.2 (1) Accessible
CPU modules
9202h
System error
• Please consult your local Mitsubishi
representative.
9204h
920Ah
9920h
9922h
9923h
9E20h Processing code error
The issued processing code cannot
be processed on the other end.
• Check the CPU(s) on the access
route.
9E81h Device type error
The device type specified for the
access target station is invalid.
• Correct the device type entered in
[Device tag settings].
9E82h Device No. error
The device number specified for the
access target station is out of range.
• Correct the device number entered
in [Device tag settings].
9E83h
Number of device points
error
The device points specified for the
access target station is out of range.
• Correct the device points entered in
[Device tag settings].
B000h
to
BFFFh
Errors detected in CC-Link IE Field Network