Mitsubishi Electronics QJ7MES96 Thermostat User Manual


 
7
- 136
7.13 Online - Remote operation
7.13.1 Checking the operation status of the MES interface function
7
MES INTERFACE FUNCTION CONFIGURATION TOOL
7.13.1 Checking the operation status of the MES interface function
The operation status of the MES interface function and the error status of the MES
interface module can be checked.
The following explains the display of [Module status].
The display of [Module status] is updated every 3 seconds.
(1) [Operation status]
(2) [Error status]
Figure 7.106 [Module status]
Table 7.93 Items displayed for [Operation status]
Display Description
Running Displayed when the MES interface function is running.
Stop
Displayed when the MES interface function is stopped.
(Even if trigger conditions are met, no job will be executed during stop of
the function.)
Initializing
Displayed during the operations indicated below.
• Perform [Update settings]
• Power OFF and then ON
• Reset the programmable controller CPU
(Even if trigger conditions are met, no job will be executed during
initialization.)
Stopping
Displayed when the operation status of the MES interface function is
changing to the [Stop] status.
Getting status
Displayed when MES Interface Function Configuration Tool is acquiring
the status data from the MES interface module.
Acquirement failed
Displayed when MES Interface Function Configuration Tool has failed in
connection for acquiring the status data from the MES interface module.
Table 7.94 Items displayed for [Error status]
Display Meaning
None Displayed when the MES interface module is operating normally.
Continuation error
Displayed when a module continuation error has occurred in the MES
interface module.
Section 10.1.2 Error types
Stop error
Displayed when a module stop error has occurred in the MES interface
module.