Mitsubishi Electronics QJ7MES96 Thermostat User Manual


 
10
- 12
10.2 Error Code List
10.2.1 Error codes for the MES interface module
10
TROUBLESHOOTING
(From the previous page)
(To the next page)
Table 10.3 Error codes for the MES interface module
Error code Error name Description Action
0A00h Initialization error
The CompactFlash card may be
corrupted.
• Replace the CompactFlash card.
0A01h Start error
0A02h Stop error
0A03h Reset error
0A04h Tag related error Tag related error
• Check if the network on the
programmable controller CPU side
is normal.
0A05h System error
• Please consult your local Mitsubishi
representative.
0A06h
Initial SNTP server time
enquiry error
The initial SNTP server time enquiry
failed, and thereby the module started
the operation synchronizing the time
with CPU No.1.
• Check for any fault on the network
connected to the specified SNTP
server computer.
• Check if the clock time is
synchronized between the specified
SNTP server and the host server
correctly.
• Check that the time of the specified
SNTP server has not been manually
changed.
0A07h
SNTP server time enquiry
error
Failed in the SNTP server time
enquiry.
0A08h
to
0A0Dh
Setting read error
The CompactFlash card may be
corrupted.
• Replace the CompactFlash card.
0A0Fh CF access stopped error
No CompactFlash card has been
installed.
File access is stopped (X2 is ON).
• Install a CompactFlash card.
• Turn the power OFF and ON, or
reset the programmable controller
CPU.
0A11h No CF card installed
No CompactFlash card has been
installed.
• Install a CompactFlash card.
0A12h
CF directory operation
error
The CompactFlash card may be
corrupted.
0A13h
Transferred setting file
check error
The setting file written to the module is
invalid.
The CompactFlash card may be
corrupted.
0A14h Setting file check error
The setting file is invalid.
The CompactFlash card may be
corrupted.
0A80h
to
0A83h
System error
• Please consult your local Mitsubishi
representative.
0A84h Illegal action setting error
Some action set in the job has an
illegal part.
• Check the actions in [Job settings].
• In Job List of [Remote operation],
the job having any illegal action can
be checked. (Such a job is not
displayed.)
0B00h
to
0B0Ah
System error
• Please consult your local Mitsubishi
representative.