Mitsubishi Electronics QJ7MES96 Thermostat User Manual


 
7
MES INTERFACE FUNCTION CONFIGURATION TOOL
7.11 Job Setting - Actions
7.11.2 Setting items in Communication action (Select/Update/Insert/MultiSelect/Delete)
7
- 111
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETTINGS AND
PROCEDURE TO
OPERATION
5
INSTALLATION AND
UNINSTALLATION
6
FUNCTIONS
7
MES INTERFACE
FUNCTION
CONFIGURATION TOOL
8
DB CONNECTION
SERVICE AND
SETTING TOOL
2) Send notification of this exception
When the [Send notification of this exception] box is checked, if multiple
records to be selected, updated or deleted exist, a value will be assigned to the
specified tag component.
When [Send notification of this exception] is selected, set a tag component to
which the value is assigned.
Tag, Component
Select a tag component to which a value is assigned.
Note that the following tags are not selectable.
Tags for which [Prohibit data writing] is enabled.
Tags for which [Array setting] is set.
Substitute value
Directly enter a substitute value.
The following lists values that can be entered as a substitute value.
3) Continue this job/Finish this job
When [Continue this job] is selected
After executions of exception processing described in the above 1) and 2),
the system continues executions of other actions.
When [Finish this job] is selected
After execution of exception processing described in 1) and 2), the job is
forcibly terminated without executing remaining actions.
At this time, update/insert/delete values before execution of the exception
processing are committed, and they are written to relevant tag
components.
(1) When a job is forcibly terminated due to exception processing, an error
occurred during job execution (job cancellation) is not notified.
Section 7.10.5 Setting items for job cancellation
(2) If [Enable DB buffering] is selected for a job, its exception process setting is
disabled.
Section 7.10.4 Setting items in DB Buffering
Table 7.77 Values that can be entered as a substitute value
Data type of tag
component
Values that can be entered as a substitute value
Bit type ON/OFF is selectable.
Single-precision type
Double-precision type
Floating-point type
Up to 16 characters
• Signed decimal notation (Example: -521.98)
• Signed exponential notation (Example: -5.2198E03)
16-bit BCD type Unsigned 16-bit BCD notation 0 to 9999 (Example: 1234)
32-bit BCD type Unsigned 32-bit BCD notation 0 to 99999999 (Example: 12345678)
Character string
Up to 32 characters
For characters that can be used for character strings, refer to the
following:
Appendix 2.3 Characters available for character string constants, etc.