Mitsubishi Electronics QJ7MES96 Thermostat User Manual


 
4
SETTINGS AND PROCEDURE TO OPERATION
4.3 Parts Names
4
- 7
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETTINGS AND
PROCEDURE TO
OPERATION
5
INSTALLATION AND
UNINSTALLATION
6
FUNCTIONS
7
MES INTERFACE
FUNCTION
CONFIGURATION TOOL
8
DB CONNECTION
SERVICE AND
SETTING TOOL
(3) Indicator LED display contents
Table 4.2 Parts names
Name Description
1) Indicator LED Refer to (3) Indicator LED display contents.
2)
10BASE-T/100BASE-TX
interface connector (RJ45)
Used for connecting a MES interface module to the following personal computers:
• Configuration computer
• Server computer
• SNTP server computer
(The MES interface module distinguishes 10BASE-T from 100BASE-TX
depending on the device on other end.)
3) Serial number display Indicates the serial number of the MES interface module.
4) EJECT button Used for ejecting a CompactFlash card from the MES interface module.
5) CompactFlash card slot Used for installing a CompactFlash card to the MES interface module.
6) CompactFlash card slot cover Cover for the CompactFlash card slot
7) Battery Battery for file protection
8) Battery connector pin
Connector pin for battery lead
(The battery lead is disconnected from the connector at shipment to prevent
battery consumption.)
Figure 4.5 LED display
Table 4.3 LED display
Name LED status Description
RUN
ON
In normal operation
(It may take some time until the RUN LED is turned ON after the module is
started.)
OFF Watchdog timer error (Hardware error)
ERR.
OFF In normal status
ON Module continuation error
Flash Module stop error
100 M
ON 100 Mbps
OFF 10 Mbps
SD/RD
ON During data send or data receive
OFF Data not transmitted
RD
SD/
100
M
10BASE-T/
100BASE-TX
RUN
ERR.
QJ71MES96