MES INTERFACE FUNCTION CONFIGURATION TOOL
7.8 Device Tag Setting
7.8.2 Setting items in Array setting
7
- 43
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETTINGS AND
PROCEDURE TO
OPERATION
5
INSTALLATION AND
UNINSTALLATION
6
FUNCTIONS
7
MES INTERFACE
FUNCTION
CONFIGURATION TOOL
8
DB CONNECTION
SERVICE AND
SETTING TOOL
7.8.2 Setting items in Array setting
An array is a data format, in which the specified number of data of the same data type are
arranged sequentially.
The Array setting is set when writing multiple records extracted from a database to the
same tag component.
Either of the following can be selected for device assignment to each tag component.
Assigning consecutive devices to each tag component (series)
Handling all tag components as a block and assigning the same kind of devices in a
series of blocks (block)
Tags with array settings are used for [MultiSelect].
(1) Use array
When the [Use array] checkbox is checked, the tag is arranged as arrays.
(2) Length of array (Range: 2 to 40000, Default: 2)
Set the number of arrays for the tag.
(3) Series/Block
Select a method for the array setting.
(a) Series
Devices of respective tag components are arranged consecutively.
(Example)When [Length of array] is set to 4 with [series] setting
Only the start device (device in n=1) need be set.
Devices in and after n=2 are configured automatically.
If any duplicate device is identified in the same tag, an error dialog box will
appear.
Check the device settings.
Figure 7.32 [Array setting]
Figure 7.33 When [series] is selected
Component_A
Component_B
Component_C
n=1
D100
to D101
ZR1000
to ZR1003
D0
n=2
D102
to D103
ZR1004
to ZR1007
D1
n=3
D104
to D105
ZR1008
to ZR1011
D2
n=4
D106
to D107
ZR1012
to ZR1015
D3