TROUBLESHOOTING
10.2 Error Code List
10.2.1 Error codes for the MES interface module
10
- 11
9
XML MESSAGE
FORMAT
10
TROUBLESHOOTINGAPPENDICESINDEX
(From the previous page)
(To the next page)
Table 10.3 Error codes for the MES interface module
Error code Error name Description Action
062Eh Data type incorrect error
There is an inconsistency between the
device and data type that were
specified in the "component setting".
(Any other than Bit was specified for a
bit device, or Bit was specified for any
other than bit device.)
• Correct the "component setting".
062Fh
Excessive number of
characters error
The number of characters specified in
the "component setting" is out of
range.
• Correct the "component setting".
0630h
Decimal/Exponential form
setting error
The decimal or exponential type
specification in the "component
setting" is invalid.
0631h
Setting file error
Failed to read out the setting file. (The
setting file is corrupted.)
• Retry writing the setting with MES
Interface Function Configuration
Too l.
0649h
064Bh
Excessive number of
device points for high
speed sampling tag
The total of device points for the high-
speed sampling tag exceeded 96.
• Change the setting so that the total
device points will not exceed 96.
064Ch
High speed sampling tag
component registration
error
Failed to register a component device
of the high-speed tag to the CPU.
• Ensure a system area in the
program memory of the
programmable controller CPU.
(Format the PLC memory.)
• For the Redundant CPU, check the
system area for the Redundant CPU
of both systems.
0650h Setting file error
Failed to read out the setting file. (The
setting file is corrupted.)
• Retry writing the setting with MES
Interface Function Configuration
Too l.
0659h
Network communication
route error
A nonexistent module was specified
for [Head I/O] in [Network
communication route] of [Access
target CPU settings].
• Correct the Head I/O address in
[Access target CPU settings].
06A0h
System error
• Please consult your local Mitsubishi
representative.
06AAh
06ABh
06ADh
0830h
Setting file error
Failed to read out the setting file. (The
setting file is corrupted.)
• Retry writing the setting with MES
Interface Function Configuration
Too l.
0831h
No CompactFlash card has been
installed.
Failed to read out the setting file. (The
setting file is corrupted.)
• Install a CompactFlash card.
• Retry writing the setting with MES
Interface Function Configuration
Too l.
0832h
Failed to read out the setting file. (The
setting file is corrupted.)
• Retry writing the setting with MES
Interface Function Configuration
Too l.
08A1h
System error
• Please consult your local Mitsubishi
representative.
08A2h
08B0h
08B1h