Mitsubishi Electronics QJ7MES96 Thermostat User Manual


 
4
SETTINGS AND PROCEDURE TO OPERATION
4.10 Removing Battery for Storage
4
- 25
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETTINGS AND
PROCEDURE TO
OPERATION
5
INSTALLATION AND
UNINSTALLATION
6
FUNCTIONS
7
MES INTERFACE
FUNCTION
CONFIGURATION TOOL
8
DB CONNECTION
SERVICE AND
SETTING TOOL
4.10 Removing Battery for Storage
When storing the MES interface module without mounting a battery, make sure to perform
the shutdown operation, then power OFF the programmable controller and remove the
battery.
Not doing so may cause the data corruption in the CompactFlash card being
accessed or a file system error.
(a) Operation procedure
1 Mount the programmable controller CPU and MES interface module on the base
unit and power ON the programmable controller CPU.
2 Stop file access.
(Turn the File access stop request (Y2) ON from OFF.)
3 Confirm that file access has stopped.
(Check the File access status (X2) is turned ON.)
4 Power OFF the programmable controller CPU.
5 Remove the battery from the MES interface module.
Figure 4.22 Removing battery for storage
File access stop request (Y2)
File access status (X2)
(During stop)
(In operation)
Power OFF the programmable controller and remove the battery.