Mitsubishi Electronics QJ7MES96 Thermostat User Manual


 
4
SETTINGS AND PROCEDURE TO OPERATION
4.8 Battery
4.8.3 Battery replacement
4
- 23
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETTINGS AND
PROCEDURE TO
OPERATION
5
INSTALLATION AND
UNINSTALLATION
6
FUNCTIONS
7
MES INTERFACE
FUNCTION
CONFIGURATION TOOL
8
DB CONNECTION
SERVICE AND
SETTING TOOL
(3) Replacement procedure of the MES interface module battery
When the MES interface module battery has been exhausted, replace the battery with
a new one according to the procedure shown in Figure 4.20.
The programmable controller must be powered ON for 10 minutes or more before
removing the battery.
Even if the battery is removed, the memory is backed up by the capacitor for a while.
However, if the replacement time exceeds the guaranteed value in the table below,
data stored in the memory may be erased. To prevent this, replace the battery quickly.
Table 4.11 Power failure compensation time
Power failure compensation time
3 minutes
Figure 4.20 Battery replacement procedure
Remove the MES interface module
from the base unit.
Battery replacement
Power OFF the programmable controller.
End
Monitor buffer
memory address 7 and check
the ON/OFF status.
ON
OFF
Power ON the programmable controller.
MES interface
module connector
MES interface module
Battery
connector
Q6BAT battery
Open the MES interface module
cover.
Remove the battery in use from the
holder.
Insert a new battery into the holder in
the right orientation, and connect the
lead connector to the connector.
Close the MES interface module
cover.
Mount the MES interface module to
the base unit.
Battery failure of the MES interface
module