Mitsubishi Electronics QJ7MES96 Thermostat User Manual


 
4
SETTINGS AND PROCEDURE TO OPERATION
4.5 Intelligent Function Module Switch Settings
4
- 11
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETTINGS AND
PROCEDURE TO
OPERATION
5
INSTALLATION AND
UNINSTALLATION
6
FUNCTIONS
7
MES INTERFACE
FUNCTION
CONFIGURATION TOOL
8
DB CONNECTION
SERVICE AND
SETTING TOOL
Use the default operation setting when changing the settings of the MES interface
module connected to the configuration computer on a 1:1 basis.
(b) Battery error detection setting (bit 2)
Set whether to detect battery errors while the MES interface module is operating
without battery. ( Section 4.9 Operation without Mounting Battery)
0: Detects battery errors.
1: Does not detect battery errors.
(3) Response monitoring time setting (Switch 3 (Lower byte))
Set the timeout time (Second) from when the MES interface module sends a request
to the access target CPU until receiving the reply.
A response time-out error (0002h) occurs if the access target CPU does not respond
within the set time.
Setting range: 15 to 255 (Second) (Default value: 15 seconds)
When setting the time between 0 and 14 or making no settings, response monitoring
time operates with 15 seconds.
After Write to PLC is executed, the intelligent function module switch settings are
enabled when turning the power ON from OFF, or resetting the programmable
controller CPU.
Remark
For GX Developer operation method, refer to the following manual.
GX Developer Operating Manual
Figure 4.10 Response monitoring time setting (Switch 3 (Lower byte))
b15 to to b0b8 b7
Specify "0".
Response monitoring time setting
(Upper byte)* (Lower byte) Switch 3
15 to 255 (Second)
When setting the time between 0
and 14 or making no settings,
response monitoring time operates
with 15 seconds.
*The upper byte data is ignored. However, when other than 0 is specified
in this area, "Switch setting error" (0180h) occurs at hardware test.