5-28 Field Control Genius® Bus Interface Unit User’s Manual
October 1999 GFK-0825F
5
Default Outputs or Hold Last State
You should also configure what type of data the Bus Interface Unit should provide to the module if
it stops receiving outputs from the network.
S1 Hld Lst State
< > tgl entr
NO
1. Select
YES
if the Bus Interface Unit should hold outputs in their last states and supply that
data to the module.
Select NO if the Bus Interface Unit should default all the module's outputs and supply that data
to the module instead.
Note:
This selection has no effect if the BIU itself fails.
2. Use the F4 (entr) key to save the selection.
If Hold Last State is set to NO, the following screen appears:
S1 Out Def Pt 01
< > tgl entr
0 0 0 0 0 0 x x
Number of the point
at the cursor location
3. On this screen, select a default state (1 or 0) for each output.
4. Use the cursor keys to select outputs. Use the F3 (toggle) key to change the state of the output
at the present cursor location.
5. Use the F4 (entr) key to save the selections.