GFK-0825F Chapter 5 Station Configuration 5-45
5
Channel Active
When a channel is configured as Active, it is scanned for data and checked for errors. If a channel
should not be scanned, that channel can be configured as inactive. An inactive input channel returns
the value 0.
S:4 CH 1
ACTIVE
< > tgl entr
1. If you want to change the displayed selection, press F3 (Tgl).
2. Use the F4 (entr) key to save the selection.
3. Press F2 ( > ) to go to the next screen.
Input Range
On this screen, specify the range for the input. There are four predetermined range and data scaling
combinations (selections 1, 2, 3, and 4), plus custom scaling.
S:4 CH1 DEF RNG
1
< > tgl entr
The default is 1. Selections 1 or 2 will convert the full input current span down to 0 milliamps and
produce negative values below 4 mA. Selection 1 produces engineering unit data in microAmps.
These also enable an "Open Wire" diagnostic bit which is true whenever the input falls below the
normal range.
Selection
Input current (µA) = Data range
1 4000 to 20000 = 4000 to 20000
2 4000 to 20000 = 0 to 32000
3 0 to 20000 = 0 to 32000
4 0 to 24000 = 0 to 32000
(none) Configurable scaling (see below)