GE GFK-0825F Carbon Monoxide Alarm User Manual


 
5-90 Field Control Genius® Bus Interface Unit User’s Manual
October 1999 GFK-0825F
5
Configure an 8-Point Analog Current Output Module
S:1 ALG330 1.0
< > del zoom
Assign I/Assign I/O References for the Module
When you “zoom” into the module's slot, a screen like this appears:
Default data len
g
th
S: 1 I * I : 032
I 00257- I 00288
< > chg ent r
Defa ult BIU data t
yp
e
Next available reference
Ba ck
p
lane Slot
This I/O reference assignment screen shows the length and the next available reference
address for each data type in BIU memory.
The 8-Point Analog Current Output Module is an intelligent module which uses more than
one type of data.
up to 8 words of analog output data (data type AQ on the Hand-held Monitor)
0-4 bytes of discrete input data (data type I) for module and channel status. Use of this
data is optional.
0-2 bytes of discrete output data (data type Q) for clearing alarms. Use of this data is
optional.
The length is displayed in units that are appropriate for the data type (analog output data is
in words, discrete inputs and outputs are in bits). The asterisk indicates that the reference
has not yet been defined.
The first screen shows references for discrete input (I) diagnostic data. You can display the
other BIU data types by pressing F3 (toggle). Press F4 (enter) when the desired data type is
displayed.
If the starting reference and length for the data type are acceptable, press F4 (enter) to
accept them. The asterisk will disappear.
S1 LOC DEF OUT
ZERO
S1 CH 1
ACTIVE
S1 CH1 DEF RNG
1
S1 CH1 SPAN L
04000
S1 CH1 ENG L
04000
S1 CH1 ENG H
20000
S1: Q * Q:016
Q00001-00016
S1 Module-> %I
DEFAULT ZERO
S1: AQ *AQ:008
AQ00001-00008
S1 Network->%AQ
DEFAULT ZERO
S1 CH1 SPAN H
20000
S1: ALG330 1.0
F4
S1: I * I:032
I00001-00016
F4, F2
F4, F2
F4, F2
F2
F1
S1 Network->%Q
DEFAULT ZERO
F2
F1
F2
F1
F2 F1
F2
F1
F2
F1
F2
F1
F2 F1
F2
F1
F2
F1
Repeat for other
channels
F2
For HHM version 4.8 or
above this channel
selection menu appears:
For HHM version 4.8 or
above press F1 from
Channel Active screen
or Up Menu key to go to
Channel Config screen.
S1 CH1 CONFIG
F4