GFK-0825F Chapter 5 Station Configuration 5-47
5
Enter the high span value for the channel. This is the actual current in microAmps to be scaled to
the high engineering units value.
S:4 CH1 EU H
32000
< > chg entr
Next, enter the actual current in microAmps to be scaled to the low engineering units value.
S:4 CH1 SPAN L
04000
< > chg entr
Span values are 16 unsigned integers ranging from 0 to 25,000. After entering the low span value
for the input, press the F4 (enter) key. Enter a high span value for the same input.
S:4 CH1 SPAN H
20000
< > chg entr
Alarm Limits
The next screen is used to set the low alarm limit for the channel in engineering units.
S:4 CH1 AL L
00000
< > chg entr
Each input channel can have a low alarm limit and a high alarm limit. Alarm limits can be set
anywhere over the dynamic range of the signal. The range for each is -32,768 to +32,767. The high
alarm limit must be greater than the low alarm limit. If alarm reporting is not wanted, alarm limits
can be set beyond the dynamic range of the signal so they will never be activated.
After entering the Low Alarm Limit, press the F4 (enter) key. Then enter the High Alarm Limit for
the channel.
S:4 CH1 AL H
32000
< > chg entr
That completes the configuration steps for one input channel on the 16-Point Grouped Analog
Input module. Continue as described above to configure the rest of the inputs.