GE GFK-0825F Carbon Monoxide Alarm User Manual


 
8-18 Field Control Genius® Bus Interface Unit User’s Manual
October 1999 GFK-0825F
8
Intelligent Modules Configuration Data Format
Configuration files of intelligent modules may exceed the 128-byte maximum length of a Genius
message. Therefore, any Write Configuration to an intelligent module must be contained within a
Begin/End Packet Sequence. The BIU rejects any Write Configuration message for an intelligent
module that does not follow a Begin Packet message.
Write Configuration for an intelligent module may be packetized by using the upper nibble of the
slot byte to indicate a packet number. Data for packets greater than zero is assumed to have an
offset with a slot configuration of (packet_number*128). Therefore, all packets except the last must
have 128 bytes.
Note that all reserved or unused bits must be 0.
Configuration Data for Intelligent Modules, Bytes 0 to 13
The first 13 bytes of configuration data for intelligent modules have the content shown below. Each
intelligent module has additional configuration data listed on the following pages.
Byte Meaning Intelligent Analog Modules (IC670…)
ALG240 ALG281 ALG282 ALG310 ALG330 ALG620 ALG630
Micro Field
Processor
(IC670MFP100)
0 intelligent module board ID 1Fh
1 reserved must be 0 0
2 unique module identifier 1 8 7 6 5 2 3 4
3 reserved must be 0 0
4 reference types word
(bit 0 = 1 means inputs available,
bit 1 = 1 means outputs available,
both = 1 means inputs and outputs
available)
3
(bits 0
and 1
both set
to 1)
333333 3
5 reserved must be 0 0
6, 7 length of module’s configuration file
in bytes
248 136 248 106 106 84 174 30
8, 9 reserved must be 0 0
10, 11 reserved must be 0 0
12 input/output hold last state/default to 0. Bits are shown below. For each, 0=default, 1-hold last state.
76543210
BSM State (read only)
BSM Present (1 = yes, 0 = no)
BSM Controller
(
1 =
y
es, 0 = no
)
BSM Forced (1 = yes, 0 = no)
CPU Redundanc
y
(
00 = no redundanc
y
01 = Hot standb
y
10 = Duplex
11 = reserved )
Duplex Default
Configuration Protection (read only)
13 reserved must be 0 0
14-n additional module data