GE GFK-0825F Carbon Monoxide Alarm User Manual


 
D-4 Field Control Genius® Bus Interface Unit User’s Manual
October 1999 GFK-0825F
D
Example 4: Discrete and Analog Data, Network and Local Processing and Group Data
Moves
In this I/O Station, there are discrete and analog I/O modules and a Micro Field Processor. Group
Data Moves are used to transfer data within the I/O Station. This configuration allows all station
inputs to be solved by the Micro Field Processor and all station outputs to be controlled by the
Micro Field Processor. The system controller (for example, a PLC) will receive all station inputs. If
the Micro Field Processor stops providing outputs, the system controller will assume control of all
station outputs.
BIU Map: I00001 - I00168
Q00001 - Q00056
AI00001 - AI00028
AQ00000 - AQ00000 (zero length)
Slot 1 synchronization is required.
Slot 1: Micro Field Processor (IC670MFP100) Reference parameters zero
length
Slot 2: High-level 16?Channel Analog Input Module
(IC670ALG240)
Reference parameters zero
length
Slot 3: 4-Channel RTD Input Module (IC670ALG620) Reference parameters zero
length
Slot 4: 8-Channel Thermocouple Input Module
(IC670ALG630)
Reference parameters zero
length
Slot 5: 16-Point 12-120 VAC Output Module
(IC670MDL330)
Q00041 - 00056
Group Move #1: Source slot 2, Destination slot 0
(move inputs from High-level Analog Input
module to BIU input tables). All submoves can be set to default to either Yes or No.
Submove 1
: (Moves diagnostic bits)
Source reference I00001
Destination reference I00001
Length 11 bytes
Submove 2:
(moves analog inputs)
Source reference AI00001
Destination reference AI00001
Length 32 bytes
Group Move #2: Source slot 0, Destination slot 2
(move outputs from BIU tables to High-level
Analog Input module control outputs).
Submove 1
: Source reference Q00001
Destination reference Q00001
Length 2 bytes