GFK-0825F Chapter 5 Station Configuration 5-83
5
S:1 AQ *AQ:008
AQ00025-00032
< > chg entr
You can edit this screen or accept it using the F4 (enter) key. The asterisk beside the data type
disappears, to show that the current values have been saved. Valid values for analog output data
length are 0-8. If this length is set to less than 8 and the module has not been previously configured
the outputs of unused channels will go to 0mV. However, if the module has been configured
previously and is reconfigured to use fewer channels, the channels that are "removed" will continue
to output voltage at their previously-configured levels until the module is reset.
S:1 AQ AQ:008
AQ00025-00032
< > chg entr
Pressing F2 (>) moves you to the screen that shows the module's discrete output bits, which can be
used by the host for clearing faults. Valid lengths for this data type are 0-16. The data must lie on
byte boundaries; entered lengths and reference addresses are automatically adjusted if necessary.
S:1 Q * Q:016
Q01817-01832
< > chg entr
Edit the reference address and length if needed. Press F4 (enter) to save the selections.
Entries must be made for data types I, Q, and AQ. If you do not want to use one of these data types,
give it a length of zero.
If you back out before all data types have been configured, the HHM displays the following screen:
Cfg Incomplete
Clear Slot?
yes no
If you exit, the I/O configuration choices are not saved.
The BIU will not send commands to the module until all three data types (I, Q, and AQ) have been
configured.