GFK-0825F Chapter 5 Station Configuration 5-69
5
RTD Type
Select the RTD type that most closely matches the RTD used on that channel. The table below has
more information about RTD categories.
S:1 CH1 RTD TYPE
100 PT 385
< > tgl entr
1. Use the F3 (toggle) key if you want to change the displayed RTD type.
2. Use the F4 (enter) key to save the selections on this screen and go on to the next item.
Selection Comments Selection Comments Selection Comments
10 PT 10 Ohm Platinum (PT) 100 PT 3916 100 Ohm Platinum,
alpha
=.003916
100 NI 618 100 Ohm Nickel At 0 deg. C,
DIN43760,
alpha
=.00618
25 PT 25 Ohm Platinum IPTS-68 1K PT 375
1 KOhm Platinum,
alpha
=.00375
120 NI 672
120 Ohm Nickel, at 0 deg. C,
alpha
=.00672
25.5 PT 392
25.5 Ohm Platinum,
alpha
=.00392 at 0 deg. C Lab Std
10 CU 10 Ohm Copper, at
25deg. C, IPTS-68
604 NI/FE 518 604 Ohm Nickel/Iron, at
0deg. C,
alpha
=.00518
100 PT 385 100 Ohm Platinum,
DIN43760,
alpha
=.00385
9.035 CU 427 9.035 Ohm Copper, at
25deg. C,
alpha
=.00427
IK NI/FE 527 1 KOhm Nickel/Iron, at
70deg. F,
alpha
=.00527
100 PT 3902 100 Ohm Platinum,
alpha
=.003902
50 CU 427 50 Ohm Copper,
alpha
=.00427
500 OHM Select UNITS of 1/10 Ohms
100 PT 392 100 Ohm Platinum,
alpha
=.00392 IPTS-6 8
100 CU 427 100 Ohm Copper,
alpha
=.00427
3000 OHM Select UNITS of 1/10 Ohms
100PT 3923 98.13 Ohm Platinum,
alpha
=.003923
100 NI 100 Ohm Nickel,
IPTS-68
Wire Type
Next, specify the type of field wiring present at the terminal board connectors for each RTD. The
choices are 3 WIRE and 4 WIRE.
S:1 CH1 WIRE TYP
3 WIRE
< > tgl entr
1. Use the F3 (toggle) key if you want to change the displayed RTD Wire type.
2. Use the F4 (enter) key to save the selections on this screen and go on to the next item.