5-50 Field Control Genius® Bus Interface Unit User’s Manual
October 1999 GFK-0825F
5
Configure Data Defaults
For data types AI and I, you can determine what the BIU should do with the module's data if the
BIU loses communications with the module. Data can either be held at its present values or
defaulted to zero.
You can accept DEFAULT: ZERO with the F4 (enter) key, or press F3 (toggle) then F4 (enter) to
change to DEFAULT: HOLD and save it.
S:2 Module-> %I
DEFAULT:ZERO
< > tgl entr
S:2 Module-> %I
DEFAULT:HOLD
< > tgl entr
S:2 Module-> %AI
DEFAULT:ZERO
< > tgl entr
For data going to the module (type Q) which is included within the BIU's I/O map, you can
determine what data the BIU will send to the module if the BIU loses communications with the
network.
S:2 Network-> %Q
DEFAULT:ZERO
< > tgl entr