5-80 Field Control Genius® Bus Interface Unit User’s Manual
October 1999 GFK-0825F
5
Offset
The last selection for each channel is Offset. This parameter is normally left at zero.
The Offset is an optional fixed value that can be used to adjust for differences in thermocouples
when the configured engineering units are either degrees C or degrees F. For example, if a
thermocouple reads 25.3 degrees C when the actual temperature is known to be 25.0 degrees C, a
value of -30 would be entered to cause the thermocouple to read 25.0 degrees.
The value contains two decimal places and should be supplied in the units specified by the Range
Type. The value is applied before high and low alarm checks.
S:1 CH1 OFFST.01
00000
< > chg entr
1. Use the F3 (change) key if you want to change the Offset, and enter the new value.
2. Use the F4 (enter) key to save the selections on this screen and go on to the next item.
Configure the Next Channel
Continue to configure the next channel in the same manner.