GFK-0825F Chapter 5 Station Configuration 5-41
5
After “entering”the correct length, the offset (starting reference) screen appears. The BIU
automatically supplies the next available address in the selected table. You can press F4 (enter) to
accept this value, or F3 (clear) then enter a new value from the keypad. Press the F4 (enter) key
after entering a new offset.
S:4 AI AI:016
Ref Addr 01896
< > clr entr
The 16-Point Grouped Analog Input Module is an intelligent module, which uses more than one
type of data. Use the F2 ( > ) key to display the screen for the module's discrete input diagnostic
data.
S:4 I * I:088
I01817-01904
< > chg entr
You can edit this screen or accept it using the F4 (enter) key. The asterisk beside the data type
disappears, to show that the current values have been saved.
S:4 I I:088
I01817-01904
< > chg entr
Next, go to the screen that shows the module's discrete output references, which are used for fault
clearing.
S:4 Q * Q:016
Q01817-01832
< > chg entr
You can also edit this screen. Use the F4 (enter key) to save the selections and continue to the next
item. Note that all required references for the module must be entered. You can give a reference
parameter a length of zero if you do not want to map the data to the BIU. If you attempt to back out
before the references are all configured, the HHM displays the following screen:
Cfg Incomplete
Clear Slot?
yes no
If you exit, the references you have configured are not saved