GFK-0825F Chapter 8 Datagrams 8-27
8
Group Data Move Configuration Data Format
76543210
BSM Switch Time (0 = 2.5 sec, 1 = 10 sec
Byte 14
76543210
unlabelled bits not used
76543210
Byte 15
reserved
76543210
Byte 16 LSB
MSB
Byte 17
Series Six/Series Five Reference Address
(Read Only)
76543210
Byte 18
Configuration Length (unused)
(# bytes in Write Configuration Sequence)
76543210
Byte 19
Diagnostic Length (# bytes) read only (unused)
76543210
Bytes
20 to 26
reserved
76543210
BSM State (read only)
BSM Present (1 = yes, 0 = no)
BSM Controller (1 = yes, 0 = no)
BSM Forced (1 = yes, 0 = no)
Bytes 0 to 11 must be: FF hex, 0,0,0,0,0,0,0,0,0,0,0
Byte 12
76543210
Byte 13
Serial Bus Address (read only)
Baud Rate Code (read only)
CPU Redundancy ( 00 = no redundancy
01 = Hot standby
10 = Duplex
11 = reserved )
Duplex Default
Configuration Protection (read only)
0 = 153.6Kb ext
1 = 153.6 Kb std
2 = 76.8 Kb
3 = 38.4 Kb
Fault Reporting Disabled (0 = yes, 1 = no)
76543210
Byte 27
Sync Module Present (slot 1=bit 0, slot 8=bit 7)