GE GFK-0825F Carbon Monoxide Alarm User Manual


 
GFK-0825F Chapter 1 Introduction 1-5
1
Environmental Specifications
Vibration Modules perform well where vibration is a factor. Designs are shock and
vibration tested to meet the following specifications when installed on a
panel-mounted DIN rail using the clamp supplied, and with the panel-
mounting feet secured:
IEC68-2-6: 10 to 57 Hz 0.012 in displacement (peak to peak)
57 to 500 Hz at 2 g (unless otherwise specified)
IEC68-2-27: Shock: 15G, 11 milliseconds, half sine wave
Noise Modules are resistant to noise levels found in most industrial applications
when installed according to accepted practices, including proper separation
of wiring by voltage and power levels, on a conductive (unpainted) DIN rail.
The DIN rail is an integral part of the grounding system.
Modules are tested to the specifications listed in the Conformance to
Standards document (GFK-1079).
Temperature Modules operate reliably in ambient air temperatures from 0 deg. C (32 deg.
F) up to 55 deg. C (131 deg. F).
Storage temperatures are -40 deg. C (-40 deg. F) to +85 deg. C (185 deg. F).
Humidity 5% to 95%, non-condensing.
For information about installing Field Control modules, please see:
Chapter 2 of this manual. It describes installation and wiring for the Bus Interface Unit module and
terminal block.
Chapter 2 of the
Field Control I/O Modules User's Manual
. It summarizes installation instructions
for modules and terminal blocks.
The individual module datasheets included in the
Field Control I/O Modules User's Manual
,
which provide specific module wiring information.
Chapter 2 of the
Genius I/O System and Communications User's Manual
, which includes detailed
instructions for selecting and installing a Genius bus.