GE GFK-0825F Carbon Monoxide Alarm User Manual


 
5-76 Field Control Genius® Bus Interface Unit User’s Manual
October 1999 GFK-0825F
5
Circuit Configuration
The following features are configured for each channel in turn.
Channel Active
S:4 CH 1
ACTIVE
< > tgl entr
When a channel is configured as Active, it is scanned for data and checked for errors. If a channel
should not be scanned, that channel can be configured as inactive. An inactive input channel returns
the value 0.
1. If you want to change the displayed selection, press F3 (Tgl).
2. Use the F4 (entr) key to save the selection.
3. Press F2 ( > ) to go to the next screen.
Engineering Units
Specify whether the module should report values for the input as hundredths of millivolts, or as
tenths of degrees C or F.
S:1 CH1 UNITS
MV
< > tgl entr
1. Use the F3 (tgl) key if you want to change the current choice.
2. Use the F4 (enter) key to save the selection.